Please use this identifier to cite or link to this item: http://cmuir.cmu.ac.th/jspui/handle/6653943832/59540
Title: Flashover occurrence factor of insulator string with arc horn on high voltage transmission line
Authors: Weerachai Naon
Suttichai Premrudeepreechacharn
Authors: Weerachai Naon
Suttichai Premrudeepreechacharn
Keywords: Energy
Issue Date: 1-Dec-2009
Abstract: This paper describes the occurrence of flashover on insulator surface instead of between the arc horn gap on unbalance insulation double circuit high voltage transmission line, whose lower insulation side has arc horn attach at each insulator strings. Front time and amplitude of lightning strokes and interception point of lightning flash were the main factors of this study. The simulations were performed with PSCAD/EMTDC. The main conclusion from the simulation results presented in this paper is only in the case of shielding failure the steepness of wave front and the lightning current magnitude increases, the tendency of insulator surface flashover increases.
URI: https://www.scopus.com/inward/record.uri?partnerID=HzOxMe3b&scp=77954805995&origin=inward
http://cmuir.cmu.ac.th/jspui/handle/6653943832/59540
Appears in Collections:CMUL: Journal Articles

Files in This Item:
There are no files associated with this item.


Items in CMUIR are protected by copyright, with all rights reserved, unless otherwise indicated.