dc.description.abstractThis paper describes the occurrence of flashover on insulator surface instead of between the arc horn gap on unbalance insulation double circuit high voltage transmission line, whose lower insulation side has arc horn attach at each insulator strings. Front time and amplitude of lightning strokes and interception point of lightning flash were the main factors of this study. The simulations were performed with PSCAD/EMTDC. The main conclusion from the simulation results presented in this paper is only in the case of shielding failure the steepness of wave front and the lightning current magnitude increases, the tendency of insulator surface flashover increases.en_US
dc.subjectEnergyen_US
dc.titleFlashover occurrence factor of insulator string with arc horn on high voltage transmission lineen_US
dc.typeConference Proceedingen_US
article.title.sourcetitle41st North American Power Symposium, NAPS 2009en_US
article.stream.affiliationsNorthern Region Operation Divisionen_US
article.stream.affiliationsChiang Mai Universityen_US
Appears in Collections:CMUL: Journal Articles

Files in This Item:
There are no files associated with this item.


Items in CMUIR are protected by copyright, with all rights reserved, unless otherwise indicated.