Please use this identifier to cite or link to this item: http://cmuir.cmu.ac.th/jspui/handle/6653943832/60724
Title: The lightning performance of overhead distribution line installed MOV and CLAH surge arresters
Authors: T. Thanasaksiri
Authors: T. Thanasaksiri
Keywords: Physics and Astronomy
Issue Date: 12-Nov-2008
Abstract: This paper compares the lightning performance of overhead distribution line which installed two arrester types, metal oxide varistor (MOV) and current limiting arcing horn (CLAH). The performance of line which related to the insulator flashover, with and without arresters installed, has been modeled and analyzed using EMTP. The MOV arrester type gives better line lightning performance. The relatively wide arrester spacings will reduce the lightning performance. The arrester leads should be kept as short as possible. © American Institute of Physics.
URI: https://www.scopus.com/inward/record.uri?partnerID=HzOxMe3b&scp=55549084909&origin=inward
http://cmuir.cmu.ac.th/jspui/handle/6653943832/60724
ISSN: 15517616
0094243X
Appears in Collections:CMUL: Journal Articles

Files in This Item:
There are no files associated with this item.


Items in CMUIR are protected by copyright, with all rights reserved, unless otherwise indicated.