Please use this identifier to cite or link to this item: http://cmuir.cmu.ac.th/jspui/handle/6653943832/60289
Title: Ground potential rise from lightning overvoltage in communication station
Authors: T. Thanasaksiri
Authors: T. Thanasaksiri
Keywords: Computer Science;Engineering
Issue Date: 6-Oct-2008
Abstract: This paper compares the ground potential rise (GPR) from lightning overvoltage with two different grounding methods, no bonding and bonding of grounding systems, between the communication tower and main ground bar (MGB) of the TOT communication station. Direct lightning stroke to the communication tower gives the higher overvoltage than the lightning stroke on distribution overhead line and also higher than the induced voltage surge. The ground bonding gives the less lightning overvoltage when compared with no ground bonding so the ground bonding in communication station is recommended. To reduce the damage from lightning overvoltage occur to the protecting equipments especially for data transmission interface (DTI), the protectors should have a higher energy discharge capability. © 2008 IEEE.
URI: https://www.scopus.com/inward/record.uri?partnerID=HzOxMe3b&scp=52949141876&origin=inward
http://cmuir.cmu.ac.th/jspui/handle/6653943832/60289
Appears in Collections:CMUL: Journal Articles

Files in This Item:
There are no files associated with this item.


Items in CMUIR are protected by copyright, with all rights reserved, unless otherwise indicated.